Floor Outlet Installation
Composition
The Alutec range of Floor Outlets consist of the body assembly, clamping
ring and trap dip tube to create the trap where applicable. The floor gratings
are supplied as separate components.
To produce a moisture seal, the clamping ring compresses sheet waterproofing
membrane against an ‘O’ ring seal recessed into the outlet body.
Where an asphalt membrane is used, the ‘O’ ring should be removed
to allow the asphalt to be dressed into the groove.
The clamping ring incorporates a “weep hole” to allow any moisture
trapped between finished floor and the waterproofing membrane to drain away.
A plug is fitted to the weep hole to allow for pipe pressure testing after
installation. Thereafter the plug should be removed and discarded.
The trap dip tube can be cut on site to suit various levels of screed. The
floor outlet body has an integral stop to prevent the trap dip tube from
projecting too far into the body. The trap dip tube is designed to fit between
the two parts of the floor grating and is supplied with a rubber sealing
gasket to make a waterproof joint.
The range of grate assemblies available suit virtually any floor finish.
The 150mm spigot length can be cut to size giving greater flexibility when
installing to different screed thickness. The grates also allow for rotation
to suit tile grids. The clamping ring supplied with both the untrapped and
trapped floor outlets is reversible and can be installed in a high or low
position. The following table shows the height variation with the clamping
ring in either the high or low position.
Floor grates - height
Variation
Spigot
Length mm |
High
Position |
Low
Position |
| 150 |
83-138mm |
49-74mm |
Connections
Alutec Floor outlet spigots are suitable for direct connection to 75mm/100mm
I.D (82mm/110mm O.D) BS4660: 1989 / BS EN1401: 1998 PVCu underground drainage
pipework. To connect to clayware drainage systems Marley adaptors, UCA40
and UCA41 can be used. For the 75/82mm outlet version, a reducer, URM304
will also be required. The Floor outlet spigots are also compatible with
cast iron pipework to BS416/EN877.
Side inlet connections
The side inlet boss versions of trapped outlets: DF335, DF435, DF345 have
a 2” BSP female thread to BS21.
• To connect to muPVC or ABS solvent weld pipework to BS5255: 1989,
use connector, code: DRH9.
• To connect to copper pipework, use proprietary male iron to copper
fitting or adaptor, DRA2 with coupling, DRH5. • To connect to cast iron pipework to BS416/EN877, use adaptor, DRA2
and coupling DRH5.
PTFE tape should be used on threaded joints.
Maintenance
Both trapped and untrapped floor outlets should be periodically inspected.
Trapped units should have the grate and trap dip tube removed and any accumulated
silt cleared from the sump on a regular basis.
All grates should be removed and periodically cleaned with a hard bristle
brush to remove any accumulation within the grating slots.
Air Pressure Testing
Air pressure testing of trapped floor outlets connected to the drainage
system should be carried out prior to the floor screed/floor surface being
laid. To achieve a successful air test, the following is recommended:-
• All joint/seal faces must be clean and free from grit or debris.
• Prior to securing the clamping flange over the waterproofing membrane,
apply PTFE tape or silicone sealant under the washers to the four stainless
steel bolts that retain the clamping ring. This ensures air cannot escape
through the thread of the bolts when subject to a pressure test.
• To ensure an air tight seal between the waterproofing membrane and
clamping flange, apply silicone sealant Ref: SC101 to both contact faces
prior to securing flange.
• Apply silicone lubricant Ref: SZ56 to the rubber ‘T’
ring seal fitted into the clamping flange and to the grating assembly 110mm
dia inlet pipe, to allow free telescopic height adjustment of the grating.
• When assembling the grating and dip tube, ensure that the flat rubber
washer is placed under the brass funnel inlet prior to clamping down the
grating.
• Ensure that the "weep hole" in the clamping flange is
plugged off during testing. This must be removed on test completion
Example Specification
Marley Aluminium Floor Outlets
Manufacturer:
Marley Alutec Ltd
Lenham, Maidstone
Kent ME17 2DE
Tel: (01622) 858888
Fax: (01622) 858725
Code: (DF335)
Outlet
Body type: (Vertical/Horizontal untrapped Horizontal/45º
trapped) Outlet size: (100mm/110mm)
Inlet Length: (45mm 100mm 200mm) Side Inlets: (2) Code: (DFG4)
Grate Assembly: (Circular – sheet flooring/ Square –
tiled floor) |